KATUP ISOLASI PENUKAR PANAS (PA-Ol/O2 AAO22) SAAT CATU DAYA PLN GAGAL

Koes Indrakoesoema, KI and Sujarwono, Sujarwono (1998) KATUP ISOLASI PENUKAR PANAS (PA-Ol/O2 AAO22) SAAT CATU DAYA PLN GAGAL. PROSIDING SEMINAR HASIL PENELITIAN PRSG. pp. 198-203. ISSN 0854-5278

[img]
Preview
Text
0184.pdf

Download (674kB) | Preview

Abstract

ABSTRAK MODIFIKASI PROGRA SIMATIC S-5 UNTUK PENUTUPAN KAT UP ISOLASI PENUKAR PANAS (PA-OI/O2 AAO22 SAAT CATU DAYA PLN GAGAL. Untuk mengoperasikan sistem pendingin sekunder diperlukan tekanan yang cukup untuk mempertahankan air pendinginp ada Penukar Panas( Heat Exchanger).Tekanan tersebut diperlukan agar air sepanjang pipa dan pada HE tidak kosong dimana berlaku 'interlocking' bila tekanan lebih kecil dari 0,8 bar, pompa tidak dapat dihidupkan. Untuk menjaga tekanan tersebut,terdpat katup AA022. Agar motor katup tetap mempunyai tegangan apabila PLN mati, dibuat catu daya tambahan yang diambil dari UPS, dimana modi[Ikasi progranmya bekerja secara otomatis memindah catu daya dari PLN ke UPS. Dengan modifikasi program ini, katup dapat tertutup sehingga tekanan dapat dipertahankan konstan dan pompa dapat segera dioperasikan bila catu daya PLN normal kembali. Uji coba tambahan program dengan simulasi telah dilakukan dan telah berhasil mensimulasikan keadaan penutup katup. ABSTRACT MODIFICATION PROG M SIMAllC S-5 FOR CLOSING ISOLATION VALVE OF HEAT EXCHANGER (PA-Ol/02 022) DURING POWER SUPPLY FROM PLN FAILURE. In routine operation,t he secondaryc oo ing pump systemn eed a sufficient pressurei n the heat exchangers.T his pressure is needed to start the pumps, where if the setting pressure less than 0.8 bar, the interlock system not allows to start the pump. To hold the coolant in HEs and in the lower stream pipings, the motor valves PA-OI/02 AA022 are rovided at the upper stream of the cooling tower for both cooling units. Power supply for motor valve comes from PLN and when at loss of power supply, the pumps stop just as all valves on the flow lines ke to open. To hold the power supply for motor valves, supply of the motors are connectedto UPS and the Simaticp rogram is automaticallyc hanget he supply from PLN to UPS for closing the valves. The expe. ent of program simulation has been done with the result the valves are closed.

Item Type: Article
Subjects: Reaktor Nuklir > Teknologi Reaktor > Sistem Reaktor
Divisions: Pusat Reaktor Serba Guna
Depositing User: EDITOR PRSG BATAN
Date Deposited: 27 Jul 2018 04:10
Last Modified: 27 Jul 2018 04:10
URI: http://repo-nkm.batan.go.id/id/eprint/3506

Actions (login required)

View Item View Item